Home/Products/Controllers/SLC-220/BASIC Smart Leakwise Controller
Controllers

SLC-220/BASIC Smart Leakwise Controller

SLC-220/BASIC Smart Leakwise Controller

The SLC-220/BASIC Smart Controller

The SLC-220/BASIC Smart LEAKWISE Controller is a digital signal processor that interfaces with up to two LEAKWISE ID-220 series sensors, providing hydrocarbon spill/leak alerts, including layer buildup and thickness indication. Alerts are transmitted via a variety of outputs and communication interfaces for local or remote reporting. The SLC-220/BASIC’s modular design and flexible configuration offer solutions for specific customer needs. It can be AC or DC line or battery powered and can operate in wired and/or wireless applications.

Features:

  • Low-power consumption with wired or wireless connection to customer’s main control system.
  • Low-cost cellular wireless operation by text messaging to cellphones or remote computers, with optional communication to a Smart LEAKWISE Receiver (SLR-220).
  • Built-in self-diagnostics of the LEAKWISE Sensors and the SLC-220 controller.
  • Easy firmware updates can be done by the user, for ongoing product improvements.

SLC-220 Operation:

Designed for low-power consumption, the SLC-220/BASIC powers on each monitored sensor briefly for sampling and decision-making before turning it off.

All settings and calibration parameters can be adjusted locally or remotely through:

  • LCD screen with touch operation (if installed) or RS-232 connection to a PC with the SLC-Manager PC Program
  • Control room connection via Modbus (RS-232 or RS-485)
  • Cellular phone messaging (if a cellular modem is installed)

Communication: cellular modem and SLR-220 receiver

When equipped with a cellular modem, the SLC-220/BASIC can report to multiple remote locations by sending text messages to up to six cell phone recipients and up to two remote modems. An SLR-220 can be one of the messages recipients. The SLR-220 receives and processes data from one or more remote SLC-220 Controllers for up to four remote sensors, and then reports to the central control room SCADA via Modbus, dry contacts, or 4-20mA output. SLC-220 verifies timely reporting from all remote sensors, providing information such as sensor name, status and signal value.

SLC-220/BASIC standard configuration:

The SLC-220/N4/LI/RL-420/COM/BASIC configuration includes:

  • RS-232 port for setup and calibration using the included SLC-Manager PC program
  • RS-485 port for interfacing with control systems (e.g., SCADA) via Modbus protocol, enabling setup and status updates
  • Full support for one LEAKWISE ID-220 Series Sensor
  • One Outputs board with five relays and one 4-20mA analog output
  • NEMA 4X (IP65) enclosure
  • Front panel status lights with two operational modes

SLC-220/BASIC Options:

  • Additional Outputs board (up to two in total, for full support of two sensors)
  • 3-inch color LCD with backlight and touch operation on front panel for easy local viewing, setting, and calibration
  • Cellular modem: LTE modem with omnidirectional antenna for wireless communication
  • Zener Safety Barriers for connecting sensors in hazardous areas
  • Hazardous area enclosure options: Exd or NEMA 7 (also IP65)
Download PDF

SLC-220/BASIC Smart Leakwise Controller Specifications:

The SLC-220/BASIC Smart Leakwise Controller is a digital signal processor for full support of up to two LEAKWISE ID-220 Series Sensors.

Key features:

  • Communication possibilities: Modbus through RS-485 or RS-232, optional cellular connectivity
  • Low power consumption
  • Outputs: up to 5 relays per sensor (dry contact SPDT), one analog 4-20 mA per sensor, Status Lights on front panel
  • SLC-Manager PC program for system setting and calibration
  • Optional 4.3″ color LCD touchscreen on front panel
  • Flexible power options: AC, DC, or battery
  • Optional Intrinsic Safety compatibility for the sensors (Zener Safety Barriers)
  • Various enclosure options: IP65 / NEMA 4X (for safe areas) or NEMA 7 / Exd (for hazardous areas)
  • Wide operating temperature: -20 °C to +70 °C

Suitable for diverse industrial applications, the SLC-220/BASIC, together with a LEAKWISE sensor, offers advanced monitoring and flexible integration for reliable hydrocarbon leak detection, monitoring and reporting.

Sensor SupportFul support up to two LEAKWISE ID-220 series sensors.
Measurement Resolution0.1% of sensor’s output signal
Status LightsTwo configurable options:
  • Default: Water, Oil, High Oil, Air, Fail, Power On: Six status lights common to all connected sensors.
  • Option: Oil 1, Oil 2, Oil 3, Oil 4 (Oil or High Oil per connected sensor), Fail (common to all connected sensors), Power On.
Display (Optional)LCD display installed on the front panel: 4.3” color LCD, 480 x 272 resolution, with backlight and touch operation. Password protected. For configuration and calibration parameters setting and system status continuous viewing.
Serial PortsThree serial communication ports
  • 1 x RS-232 for configuration and calibration parameters setting (interface with PC/Laptop at 57,600 bps, 8 data bits, no parity, 1 stop bit
  • 1 x RS-232 port for optional cellular modem, at 57,600 bps, 8 data bits, no parity, 1 stop bit, HW flow control
  • 1 x RS-485 half-duplex port for communication to SCADA via Modbus protocol, at 57,600 bps, 8 data bits, no parity, 1 stop bit, settable slave address
  • 1 x RS-485 half-duplex port – optional

Outputs Board:

Up to two boards can be installed. One Outputs Board is supplied inside each controller, a second board is optional. Each Outputs Board includes:

  • Five dry contact relays: A separate SPDT relay (N.O. and N.C. contacts, rated 6A at 250 VAC or 30 VDC) for Water, Oil, High Oil, Air and Fail indication for one sensor. May be used in Fail Safe mode: Each board can be set up to serve four sensors. The relays will indicate Oil / High Oil for sensor 1, Oil / High Oil for sensor 2, etc., and the Fail relay will be common to all sensors.
  • One 4-20 mA output: Current source analog output indicating measured oil layer thickness and trend. User-configurable (by jumpers) to 4-20 mA, 0-20 mA, 0-24 mA or 0-5V output range.
  • Maintenance test for the relays and 4-20mA output (jumper enabled).
Operation & DiagnosticBuilt-in test for sensors and system diagnostics. SIL 2 verified
FirmwareMain Board firmware upgradeable through the PC RS-232 serial port.
Cellular ModemOptional, LTE network compatible.

Cellular modem and omnidirectional antenna to enable wireless remote reporting and setting to/from up to six cellular phones and two remote modems. SIM card supplied by user.

Installation DistanceMaximum distance to LEAKWISE ID-220 series sensors is 1,200m (4000 ft.), subject to hazardous area restrictions and use of Zener Safety Barriers. Two sets of Zener Safety Barriers can be installed in all enclosure types.
Power SupplyThree options for system power supply
  • 110/220VAC (80-264 VAC, 50/60 Hz)
  • 12 or 24VDC
  • Ability to operate from a Optional solar panel with 12VDC battery and charger (third party supply).
Power Consumption6.2W maximum, not including an optional cellular modem.
EnclosureNEMA 4X (UL for USA and Canada) or IP65, for non-hazardous areas. (other enclosure options are available, see Enclosures & options)
Dimensions297 x 297 x 191 mm (11.69 x 11.69 x 7.52 in) for NEMA 4X / IP65 enclosure

Ambient Temperature:

  • Controller with 12 or 24 VDC input voltage: -40 °C to +85 °C
  • Controller with 100-240VAC input voltage: -20 °C to +70 °C; Lower range available.
  • Controller with LCD display: -20 °C to +70 °C
  • Controller with cellular modem: -20 °C to +55 °C
Humidity5 to 95% non-condensing
Power consumption calculationLow-power consumption when Outputs Boards or LCD are not in use.
  • Each sensor consumes 120mW maximum; [four sensors = 0.12W max, since sensors are turned off when not sampled].
  • The LCD display consumes 0.6W maximum with backlight, which is dimmed when not used for 15 minutes.
  • Each Outputs Board consumes 2.6W maximum [two output boards at 5.2W max].

Total:

6.2W maximum, not including a cellular modem.

Enclosure Options:

  • NEMA 4X (UL for USA and Canada) or IP65, for non-hazardous areas. Dimensions: 297 x 297 x 191 mm (11.69 x 11.69 x 7.52 in).
  • ATEX and IECEx Flameproof, certified as II2(1)GD – Ex db [ia Ga] IIB+H2 T6 Gb IP66. Dimensions: Depends on the actual enclosure in use.
  • UL for USA & Canada, Explosionproof NEMA 7 for Class I Groups B, C & D, also NEMA 4. Dimensions: Depends on the actual enclosure in use.
  • Controller without enclosure (Back Plate) for installation in a user-cabinet. Dimensions: 269 x 269 x 150 mm (10.6 x 10.6 x 5.9 in).
OPTIONSDisplay: LCD display installed on the front panel: 4.3” color LCD, 480 x 272 resolution, with backlight and touch operation. Password protected. For configuration and calibration parameters setting and system status continuous viewing.
Safety Safety BarriersZener Safety Barriers installed inside the enclosure, in series with sensor cable. Up to two sets of safety barriers can be installed inside SLC-220/BASIC.

LTE network compatible. Cellular modem and omnidirectional antenna to enable wireless remote reporting and setting to/from up to six cellular phones and two remote modems. SIM card supplied by user.

SLR-220 Receiver:

A special version of SLC-220 for interfacing up to four locally wired or remote sensors. A remote sensor is wired to a remote SLC-220/BASIC or SLC-220/MULTI. The SLR-220 and SLC-220 controllers are equipped with cellular modems for communicating the remote sensors to the SLR-220.

Customize your monitoring solution